Heat Exchanger C Series

The Heat Exchanger C Series removes heat from the convey air using coolant or cooled water.

FEATUREs

  • PRESSURE HOUSING:
    • Cores are removable through both the front and back sides of the housing, without disassembly of the gas duct.
    • Pressure tests from a full vacuum to 22.5 PSIG are available.
    • Housings can be built to contain several cores with separate or shared access panels.
    • Mist eliminators can also be built into a housing to prevent condensed moisture from carrying downstream.
    • The gas connection size and type can easily be changed to match system requirements.

 

  • FIN-TUBE CORE:
    • The fins are rectangular plates with a matrix of die-extruded tube collars.
    • A sheet metal casing provides rigidity to the fin-tube assembly prior to tube expansion.
    • After assembly, the tubes are expanded into the fin collars, giving a gap-free connection, maximizing heat transfer and structural integrity.

 

  • INSTALLATION CONSIDERATIONS:
    • The fluid circuit consists of several parallel tube circuits, which are joined at inlet and outlet headers.
    • The circuits are designed to work “downhill” to prevent trapping; but to assure complete drainage, optional intermediate drain headers are available.
    • Attached at the 180-degree return bends, they provide positive water drainage and protection from freeze-up.
    • To prevent metal work-hardening and failure, it is important to isolate the exchanger from vibration.
    • Pulsating flow produced by rotary lobe blowers must be dampened by a chambered silencer.